Superhigh Direct Current Switching Failure
DOI:
https://doi.org/10.51501/jotnafe.v8i1.482Abstract
A technician was injured by steam and boiling water when the cooling jacket exploded on a shorting switch. The shorting switch was being used to make 130,000 amps d.c. bypass an electrochemical cell so the cell could be removed from the production line for repairs. Prior problems had resulted in a cold soldered joint in the connecting arm for the switch. Then when the current overheated the electrically weakened joint mechanical strain on the arm caused part of the cable to loosen rapidly increasing the heat and causing explosive failure of the water jacket.Published
1991-01-01
How to Cite
Tims, Eugene F. 1991. “Superhigh Direct Current Switching Failure”. Journal of the National Academy of Forensic Engineers 8 (1). https://doi.org/10.51501/jotnafe.v8i1.482.
Issue
Section
Articles
License
Copyright (c) 1991 National Academy of Forensic Engineers
This work is licensed under a Creative Commons Attribution-NoDerivatives 4.0 International License.
All rights © Journal of the National Academy of Forensic Engineers.
Full statement regarding the author's license of copyright to the NAFE is shown on the Copyright section of the Submissions Page.